Name
Type
Default
Description
RST_LKOUT
BOOLEAN
0=False
Reset lockout
RST_ALARM
BOOLEAN
0=False
Reset traveling time
alarms
9.12.7.2
HSABTC Output signals
Table 1609: HSABTC Output signals
Name
Type
Description
READY
BOOLEAN
Ready for transfer
NOT_READY
BOOLEAN
Not ready for transfer
TR_RUNNING
BOOLEAN
Transfer is in running state
NOT_IDLE
BOOLEAN
Transfer is not in idle state
LOCKOUT
BOOLEAN
Transfer lockout status
FAST_READY
BOOLEAN
Ready for fast transfer
OPEN_CB1
BOOLEAN
Open command for feeder 1
breaker
CLOSE_CB1
BOOLEAN
Close command for feeder 1
breaker
OPEN_CB2
BOOLEAN
Open command for feeder 2
breaker
CLOSE_CB2
BOOLEAN
Close command for feeder 2
breaker
OPR_LOADSHED
BOOLEAN
Activate load shedding
CB_DECOUPL
BOOLEAN
CB decoupling activated
COMPL_FAST
BOOLEAN
Fast transfer complete
COMPL_FBBM
BOOLEAN
Fast break before make
transfer complete
COMPL_1ST_PH
BOOLEAN
First phase coincidence
transfer complete
COMPL_RES
BOOLEAN
Residual voltage based trans-
fer complete
COMPL_TDLY
BOOLEAN
Time delayed based transfer
complete
TR_CANCEL
BOOLEAN
Transfer cancelled
FRQDIFF_FAIL
BOOLEAN
Frequency difference is not in
range for fast transfer
ANGDIFF_FAIL
BOOLEAN
Phase angle difference is not
in range for fast transfer
GRAD_FAIL
BOOLEAN
Frequency gradient over per-
missible for 1st phase trans-
fer
Table continues on the next page
1MRS759142 F
Control functions
REX640
Technical Manual
1799