3.19.5.2
Functionality
The GOOSE data health function T_HEALTH evaluates enumerated data of “Health”
data attribute. This function block can only be used with GOOSE.
The
IN
input can be connected to GOOSERCV_ENUM function block, which is
receiving the LD0.LLN0.Health.stVal data attribute sent by another device.
The outputs
OK
,
WARNING
and
ALARM
are extracted from the enumerated input value.
Only one of the outputs can be active at a time. In case the GOOSERCV_ENUM
function block does not receive the value from the sending device or it is invalid, the
default value (0) is used and the
ALARM
is activated in the T_HEALTH function block.
3.19.5.3
Signals
Table 163: T_HEALTH Input signals
Name
Type
Default
Description
IN1
Any
0
Input signal
Table 164: T_HEALTH Output signals
Name
Type
Description
OK
BOOLEAN
Output signal
WARNING
BOOLEAN
Output signal
ALARM
BOOLEAN
Output signal
1MRS759142 F
Basic functions
REX640
Technical Manual