Signals
Table 195: TPGAPC Input signals
Name
Type
Default
Description
IN1
BOOLEAN
0=False
Input 1
IN2
BOOLEAN
0=False
Input 2
Table 196: TPGAPC Output signals
Name
Type
Description
OUT1
BOOLEAN
Output 1 status
OUT2
BOOLEAN
Output 2 status
Settings
Table 197: TPGAPC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Pulse time
0...60000
ms
1
0
Minimum pulse time
3.20.1.2
Minimum pulse timer second resolution, two channels TPSGAPC
(ANSI 62TPS)
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Minimum pulse timer second reso-
lution, two channels
TPSGAPC
TPS
62TPS
Function block
Figure 122: Function block
Functionality
The minimum pulse timer second resolution, two channels, function TPSGAPC
contains two independent timers. The function has a settable pulse length (in
seconds). The timers are used for setting the minimum pulse length for example,
the signal outputs. Once the input is activated, the output is set for a specific
duration using the
Pulse time setting. Both timers use the same setting parameter.
Basic functions
1MRS759142 F
232
REX640
Technical Manual