DOPPDPR Input signals
Table 1002: DOPPDPR Input signals
Name
Type
Default
Description
I3P
SIGNAL
-
Three-phase currents
U3P
SIGNAL
-
Three-phase voltages
BLOCK
BOOLEAN
0=False
Block signal for acti-
vating the blocking
mode
DOPPDPR Output signals
Table 1003: DOPPDPR Output signals
Name
Type
Description
OPERATE
BOOLEAN
Operate
START
BOOLEAN
Start
4.8.2.8
DOPPDPR Settings
Table 1004: DOPPDPR Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Start value
0.01...2.00
xSn
0.01
1.00
Start value
Operate delay time 40...300000
ms
10
40
Operate delay time
Directional mode
2=Forward
3=Reverse
2=Forward
Directional mode
Power angle
-90...90
deg
1
0
Adjustable angle
for power
Table 1005: DOPPDPR Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation On/Off
Measurement
mode
1=PhsA, PhsB, PhsC
2=Arone
3=Pos Seq
4=PhsAB
5=PhsBC
6=PhsCA
7=PhsA
8=PhsB
9=PhsC
3=Pos Seq
Selection of power
calculation method
Protection functions
1MRS759142 F
1070
REX640
Technical Manual