Name
Type
Values (Range)
Unit
Description
4=test/blocked
5=off
DPHHPDOC Monitored data
Table 411: DPHHPDOC Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start time / op-
erate time
DIR_A
Enum
0=unknown
1=forward
2=backward
-1=both
Direction phase A
DIR_B
Enum
0=unknown
1=forward
2=backward
-1=both
Direction phase B
DIR_C
Enum
0=unknown
1=forward
2=backward
-1=both
Direction phase C
ANGLE_A
FLOAT32
-180.00...180.00
deg
Calculated angle differ-
ence, Phase A
ANGLE_B
FLOAT32
-180.00...180.00
deg
Calculated angle differ-
ence, Phase B
ANGLE_C
FLOAT32
-180.00...180.00
deg
Calculated angle differ-
ence, Phase C
VMEM_USED
BOOLEAN
0=False
1=True
Voltage memory in use
status
DPHHPDOC
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
4.1.2.12
Technical data
Table 412: DPHxPDOC Technical data
Characteristic
Value
Operation accuracy DPHLPDOC
Depending on the frequency of the current/voltage
measured: f
n
±2 Hz
Current:
±1.5% of the set value or ±0.002 × I
n
Voltage:
±1.5% of the set value or ±0.002 × U
n
Table continues on the next page
1MRS759142 F
Protection functions
REX640
Technical Manual
367