JAMPTOC Output signals
Table 454: JAMPTOC Output signals
Name
Type
Description
OPERATE
BOOLEAN
Operate
4.1.7.8
JAMPTOC Settings
Table 455: JAMPTOC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Start value
0.10...10.00
xIn
0.01
2.50
Start value
Operate delay time 100...120000
ms
10
2000
Operate delay time
Table 456: JAMPTOC Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay time
0...60000
ms
1
100
Reset delay time
4.1.7.9
JAMPTOC Monitored data
Table 457: JAMPTOC Monitored data
Name
Type
Values (Range)
Unit
Description
START
BOOLEAN
0=False
1=True
Start
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start time / op-
erate time
JAMPTOC
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
4.1.7.10
Technical data
Table 458: JAMPTOC Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured
current: f
n
±2 Hz
±1.5% of the set value or ±0.002 × I
n
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Table continues on the next page
1MRS759142 F
Protection functions
REX640
Technical Manual