Dead bus voltage
Live bus voltage
U
BusA
U
BusB
f
BusA
f
BusB
Frequency[Hz]
∆
f
=
f
BusA
-
f
BusB
Rated frequency
Diff frequency
Diff angle
∆φ
=
∠
U
BusA
-
∠
U
BusB
Δ
U = |
U
BusA
| – |
U
Bu
sB
|
Diff voltage
Diff angle
Figure 872: Conditions to be fulfilled when detecting synchronism between systems
When the measured difference of voltages (U_DIFF_MEAS) and measured difference
in frequency (FR_DIFF_MEAS) are within the synchro check limits given in
MATCH_OK
is activated. The output
MATCH_INPRO
is activated when
the voltage and frequency matching is in progress. The matching status input is
received via
ASC1_NS_DAT
signal from ASCGAPC.
When the frequency, phase angle and voltage conditions are fulfilled, the duration
of the synchronism conditions is checked to ensure that they are still met when
the condition is determined on the basis of the measured frequency and phase
difference. Depending on the CB and the closing system, the delay between the
closing signal and the CB closing is about 50...250 ms. The selected
Closing time of
CB informs the function how long the conditions have to persist. The value covers
both the CB closing delay and the output type dependent delay. The synchro check
function compensates for the measured slip frequency and the CB closing delay.
The closing angle advance is calculated continuously:
Closing angle
= ∠
− ∠
(
)
° +
−
(
)
⋅
U
U
f
f
TCB
BusA
BusB
BusA
BusB
1000
⋅
°
360
(Equation 369)
∠ U
BusA
Measured bus A voltage phase angle
∠ U
BusB
Measured bus B voltage phase angle
TCB
Parameter
Closing time of CB
TCB
t
T
x
CB
PL
=
+
+
(Equation 370)
t
CB
CB closing delay in ms
T
PL
Output type dependent delay in ms (see
x
Hardware delays between the protection relay and CB in ms; delays due to, for
example, auxiliary relays and contactors, if used
1MRS759142 F
Control functions
REX640
Technical Manual
1593