U3P1
U3P2
U3P_BB
Note
Allowed only if Uo is
also measured from
U3P1 and U3P2
3 phase-to-ground
3 phase-to-ground
1 phase-to-ground
Supported
1 phase-to-phase
1 phase-to-phase
1 phase-to-phase
Limited functionality
1 phase-to-ground
1 phase-to-ground
1 phase-to-ground
Limited functionality
Limited functionality due to limited voltage connections is related to under-voltage
triggering. In case only one voltage is connected, function is blind to unconnected
phases. In this case external triggering is recommended.
Phase currents can be left unconnected but then circuit breaker monitoring has
limited functionality available. Recommendation is to connect full three phase
current triplet to both I3P inputs.
Table 1602: Supported current connections
I3P1
I3P2
Note
All three phases connected
All three phases connected
Recommended
Not connected
Not connected
Limited functionality
9.12.5
Operation principle
The
Operation setting is used to enable or disable the function. When selected "On"
the function is enabled and respectively "Off" means function is disabled. Function
state can be controlled also with level sensitive
TRANSFER_ON
input. If input is TRUE,
function is “On” and if input is FALSE, function is “Off”. If
TRANSFER_ON
input is not
connected in relay configuration tool, then status is “On”. The operation of HSABTC
is described by a module diagram presented in
. All the modules in the
diagram are explained in the next sections.
1MRS759142 F
Control functions
REX640
Technical Manual
1761