Earthing
contact
Disconnector
contact
Sliding part
Fixed contact
In
sulating
spindle
Protec
ti
on relay
RIO600
Motor
M
oto
r c
on
tr
ol
Commands
Status
Position
con
tacts
Reed contact
Ree
d
contac
t
Figure 838: Connection diagram for RIO600 control of a three-position switchgear
motor
When the RIO600 SCM module is selected as control mode, outputs
EXE_DCCLOSE, EXE_DCOPEN, EXE_ESCLOSE
and
EXE_ESOPEN
are
connected in Application Configuration. When direct motor control is
selected as control mode, static outputs
H_UP_LEFT, H_UP_RIGHT,
H_LO_LEFT
and
H_LO_RIGHT
are connected in Application Configuration.
9.2.6
Signals
9.2.6.1
P3SXSWI Input signals
Table 1479: P3SXSWI Input signals
Name
Type
Default
Description
DCPOSOPEN
BOOLEAN
0=False
Signal for open posi-
tion of disconnector
DCPOSCLOSE
BOOLEAN
0=False
Signal for close posi-
tion of disconnector
Table continues on the next page
1MRS759142 F
Control functions
REX640
Technical Manual
1531