Table 1439: RDRE Non group general settings (basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1
1=on
Disturbance re-
corder on/off
Record length
10...500
fundamental cycles 1
50
Size of the record-
ing in fundamental
cycles
Pre-trg length
0...100
%
1
50
Length of the re-
cording preceding
the triggering
Table 1440: RDRE Non group general settings (advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation mode
1=Saturation
2=Overwrite
1
1
Operation mode of
the recorder
Exclusion time
0...1 000 000
ms
1
0
The time during
which triggerings
of same type are
ignored
Storage rate
32, 16, 8
samples per funda-
mental cycle
32
Storage rate of
the waveform re-
cording
Periodic trig time
0...604 800
s
10
0
Time between peri-
odic triggerings
Stor. mode periodic 0=Waveform
1=Trend / cycle
1
0
Storage mode for
periodic triggering
Stor. mode manual 0=Waveform
1=Trend / cycle
1
0
Storage mode for
manual triggering
Table 1441: RDRE Control data (basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Trig recording
0=Cancel
1=Trig
0=Cancel
Trigger the disturb-
ance recording
Clear recordings
0=Cancel
1=Trig
0=Cancel
Clear all recordings
currently in memo-
ry
8.2.8
Monitored data
Table 1442: RDRE Monitored data
Parameter
Values
(Range)
Unit
Step
Default
Description
Number of re-
cordings
0...100
Number of re-
cordings cur-
rently in
memory
Rem. amount
of rec.
0...100
Remaining
amount of re-
cordings that
Table continues on the next page
Measurement functions
1MRS759142 F
1494
REX640
Technical Manual