Table 35: Secondary IP address parameters
Parameter
Options
Description
Configuration/Communication/Ether-
net/Network 2 address/ Enable
False (default)
Network 2 disabled
TRUE
Network 2 enabled
Configuration/Communication/Ether-
net/Network 2 address/IP address
0.0.0.0
IP address for Net-
work 2
Configuration/Communication/Ether-
net/Network 2 address/IP address
0.0.0.0
Subnet address for
Network 2
Configuration/Communication/Ether-
net/Network 2 address/MAC address
xx-xx-xx-xx-xx-xx
MAC address for Net-
work 2
The IP address for Network 2 is disabled by default settings, and all Ethernet
ports are assigned to the same IP address used in the Network 1 address menu
Configuration > Communication > Ethernet > Network 1. If Network 2 is taken
into use by the setting Enable="True" (requires reboot), the interlink port X3 of the
COM module is assigned to this second network, using the IP address and subnet
parameters in the Network 2 address menu Configuration > Communication >
Ethernet > Network 2 address.
If the Network 2 interface is enabled, PTP time synchronization and SMV/
GOOSE multicast are disabled for that port.
The secondary IP setting must not collide with the primary Network 1 IP
address or LHMI IP address, otherwise the secondary IP address is not
taken into use.