3.22.6.3
Signals
Table 325: NER Input signals
Name
Type
Default
Description
REAL_IN1
FLOAT32
0
Real input 1
REAL_IN2
FLOAT32
0
Real input 2
TOLR
FLOAT32
0
Tolerance for compar-
ison
Table 326: NER Output signals
Name
Type
Description
OUT
BOOLEAN
Output value
3.22.7
Real greater than or equal comparator GER
3.22.7.1
Function block
Figure 180: Function block
3.22.7.2
Functionality
The real greater than or equal comparator function GER compares the real input
REAL_IN1
with the real input
REAL_IN2
and activates the binary output
OUT
if
REAL_IN1
is equal to or greater than
REAL_IN2
-
TOLR
or greater than input
REAL_IN2
. That is, if
REAL_IN1
≥ (
REAL_IN2
-
TOLR
) or
REAL_IN1
> (
REAL_IN2
),
OUT
= 1, else
OUT
= 0.
If inputs
REAL_IN1
or
REAL_IN2
are outside the range, then
OUT
is set to 0.
Greater than region
Equal region
Max 2097151.000
REAL_IN2-TOLR
REAL_IN2
Figure 181: Region of GER comparison
1MRS759142 F
Basic functions
REX640
Technical Manual
305