- Steam power stations
- Combined cycle power plants
- Nuclear power stations
2. Environmental technology installations
- Flue gas purification
- Refuse incineration installations
3. Voltage supply to continuous industrial processes
- Chemical plants
- Industrial facilities with high degrees of automation
- Fiber manufacturing
- Petrochemical processes
A typical switchgear configuration with two circuit breakers is shown in
One of the two feeders is connected to the busbar. One of the two feeder’s circuit
breaker is closed, the other is open. A parallel operation of both feeders is not
intended. If an error leads to an interruption of the feeder currently in operation say
feeder 1, the transfer device switches the load over to the second feeder 2 in the
shortest possible time. Following successful transfer, the busbar is then supplied
by the second feeder 2. Once the main feeder 1 is again in operation, a manually-
initiated transfer back can take place and the normal status can be restored once
again. A protection-initiated transfer can be executed from either of feeder 1 or
feeder 2.
Control functions
1MRS759142 F
1788
REX640
Technical Manual