3.25.2.4
Settings
Table 352: SCHLCCH Settings
Parameter
1
Values (Range)
Unit
Step
Default
Description
Port n Mode
Off
On
Dedicated channel
2
On
Mode selection for rear port(s). If
port is not used, it can be set to
“Off”. Port cannot be set to “Off”
when
Redundant mode is “HSR”
or “PRP” and port is one of the
redundant ports (LAN A or LAN
B).
Filter Mode Xn
Off
SMV
GOOSE
GOOSE & SMV
Off
Selection for message filtering
Goose rate limiter Xn 0.512...90.000
10.000
Goose rate limit (Mbps)
SMV rate limit Xn
0.512...90.000
70.000
Sampled measured values rate
limit (Mbps)
Def. rate limit Xn
0.512...90.000
8.000
Default rate limit (Mbps)
3.25.2.5
Monitored data
Monitored data is available in six locations.
• Monitoring > Communication > Ethernet > Activity > CH1LIV
• Monitoring > Communication > Ethernet > Activity > CH2LIV
• Monitoring/ > Communication > Ethernet > Activity > CH3LIV
• Monitoring/ > Communication > Ethernet > Link statuses > LNK1LIV
• Monitoring > Communication > Ethernet > Link statuses > LNK2LIV
• Monitoring > Communication > Ethernet > Link statuses > LNK3LIV
3.25.2.6
Diagnostics
Diagnostics data is available in Monitoring > Communication > Ethernet >
Diagnostics > Xn (n = 1...3).
Table 353: Diagnostic parameters for X1/LAN, X2/LAN and X3/LAN
Parameter
Values (Range)
Unit
Step
Default
Description
Reset counters
FALSE / TRUE
FALSE
Reset counters command
GOOSE limit count
0...1000000
0
Goose rate limit exceed count
SMV limit count
0...1000000
0
Sampled measured values limit
exceed count
Ucast limit count
0...1000000
0
Unicast rate limit exceed count
Def. limit count
0...1000000
0
Default rate limit exceed count
GOOSE limit alarm
FALSE / TRUE
FALSE
Goose rate limit exceed alarm
SMV limit alarm
FALSE / TRUE
FALSE
Sampled measured values limit
alarm
Ucast limit alarm
FALSE / TRUE
FALSE
Unicast rate limit exceed alarm
Def. limit alarm
FALSE / TRUE
FALSE
Default rate limit exceed alarm
1
n = 1...3
2
Only available for port X3
1MRS759142 F
Basic functions
REX640
Technical Manual