COLPTOC Input signals
Table 1055: COLPTOC Input signals
Name
Type
Default
Description
I3P
SIGNAL
-
Three-phase currents
BLOCK
BOOLEAN
0=False
Block signal for acti-
vating the blocking
mode
CB_CLOSED
BOOLEAN
0=False
Input showing the
status of capacitor
circuit breaker
COLPTOC Output signals
Table 1056: COLPTOC Output signals
Name
Type
Description
OPR_OVLOD
BOOLEAN
Overload operated
OPR_UN_I
BOOLEAN
Operate under current
ST_OVLOD
BOOLEAN
Overload started
ST_UN_I
BOOLEAN
Under current started
ALARM
BOOLEAN
Alarm
BLK_CLOSE
BOOLEAN
Inhibit re-close of capacitor
bank
4.12.1.8
COLPTOC Settings
Table 1057: COLPTOC Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Start value over-
load
0.30...1.50
xIn
0.01
1.00
Start value for over-
load stage
Alarm start value
80...120
%
1
105
Alarm start value
(% of Start value
overload)
Start value Un Cur
0.10...0.70
xIn
0.01
0.50
Start value for un-
der current opera-
tion
Time multiplier
0.05...2.00
0.01
1.00
Time multiplier for
Capacitor Bank
protection curves
Alarm delay time
500...6000000
ms
100
300000
Alarm delay time
Un Cur delay time
100...120000
ms
100
1000
Delay time for un-
der current opera-
tion
Table 1058: COLPTOC Group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reclose inhibit time 1...6000
s
1
1
Reclose inhibit time
1MRS759142 F
Protection functions
REX640
Technical Manual
1117