HCUBPTOC Input signals
Table 1079: HCUBPTOC Input signals
Name
Type
Default
Description
I3P1
SIGNAL
-
Three-phase currents
1
I3P2
SIGNAL
-
Three-phase currents
2
BLOCK
BOOLEAN
0=False
Block signal for acti-
vating the blocking
mode
HCUBPTOC Output signals
Table 1080: HCUBPTOC Output signals
Name
Type
Description
OPERATE
BOOLEAN
Operate
START
BOOLEAN
Start
ALARM
BOOLEAN
Alarm
4.12.3.8
HCUBPTOC Settings
Table 1081: HCUBPTOC Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Start value
0.01...1.00
xIn
0.01
0.10
Start value
Alarm start value
0.01...1.00
xIn
0.01
0.05
Alarm start value
Time multiplier
0.05...15.00
0.01
1.00
Time multiplier
in IEC/ANSI IDMT
curves
Operating curve
type
1=ANSI Ext. inv.
2=ANSI Very inv.
3=ANSI Norm. inv.
4=ANSI Mod. inv.
5=ANSI Def. Time
6=L.T.E. inv.
7=L.T.V. inv.
8=L.T. inv.
9=IEC Norm. inv.
10=IEC Very inv.
11=IEC inv.
12=IEC Ext. inv.
13=IEC S.T. inv.
14=IEC L.T. inv.
15=IEC Def. Time
17=Programmable
18=RI type
15=IEC Def. Time
Selection of time
delay curve type
Table continues on the next page
1MRS759142 F
Protection functions
REX640
Technical Manual
1139