
Parameter
Values (Range)
Unit
Step
Default
Description
Start value df/dt
-0.2000...0.2000
xFn/s
0.0001
0.0100
Frequency start val-
ue rate of change
Operate Tm Freq
80...5400000
ms
10
200
Operate delay time
for frequency
Operate Tm df/dt
120...200000
ms
10
400
Operate delay time
for frequency rate
of change
Table 886: FRPFRQ Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Table 887: FRPFRQ Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay Tm
Freq
0...60000
ms
1
0
Reset delay time
for frequency
Reset delay Tm
df/dt
0...60000
ms
1
0
Reset delay time
for rate of change
4.6.1.9
FRPFRQ Monitored data
Table 888: FRPFRQ Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Start duration
ST_DUR_OFRQ
FLOAT32
0.00...100.00
%
Start duration
ST_DUR_UFRQ
FLOAT32
0.00...100.00
%
Start duration
ST_DUR_FRG
FLOAT32
0.00...100.00
%
Start duration
FRPFRQ
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
4.6.1.10
Technical data
Table 889: FRPFRQ Technical data
Characteristic
Value
Operation accuracy
f>/f<
±5 mHz
df/dt
±50 mHz/s (in range |df/dt|
<5 Hz/s)
±2.0% of the set value (in
range 5 Hz/s <
|df/dt| < 15 Hz/s)
Start time
f>/f<
<80 ms
1
Table continues on the next page
1MRS759142 F
Protection functions
REX640
Technical Manual
927