Table 77: Station authority level “L,S,S+R,L+S,L+S+R” using R/L button
L/R Control
L/R Control status
Control access
R/L button
CTRL.LLN0.LocS
ta
1
CTRL.LLN0.MltL
ev
L/R state
CTRL.LLN0.Loc
KeyHMI
Local user
IEC 61850 client
2
IEC 61850
client
3
Local
FALSE
FALSE
1
x
Remote
FALSE
TRUE
7
x
x
Remote
TRUE
FALSE
3
x
Local + Remote
FALSE
TRUE
6
x
x
x
Local + Remote
TRUE
TRUE
5
x
x
Off
FALSE
FALSE
0
Table 78: Station authority level “L,S,S+R,L+S,L+S+R” using CONTROL function block
L/R Control
L/R Control status
Control access
R/L button
CTRL.LLN0.LocS
ta
4
CTRL.LLN0.MltL
ev
L/R state
CTRL.LLN0.Loc
KeyHMI
Local user
IEC 61850 client
5
IEC 61850
client
6
CTRL_OFF
FALSE
FALSE
0
CTRL_LOC
FALSE
FALSE
1
x
CTRL_STA
FALSE
FALSE
3
x
CTRL_REM
7
TRUE
TRUE
3
x
CTRL_REM
FALSE
TRUE
7
x
x
CTRL_ALL
FALSE
TRUE
6
x
x
x
CTRL_ALL
7
TRUE
TRUE
5
x
x
3.8.8
Control mode
The function has two outputs
BEH_TST
and
BEH_BLK
which are activated in test
mode according to
Table 79: Control mode
Control mode
Description
Control BEH_BLK
On
Normal operation
FALSE
Blocked
Control function commands blocked
TRUE
Off
Control functions disabled
FALSE
For more information, see the Test mode chapter in this manual.
1
Station client reserves the control operating by writing controllable point LocSta.
2
Client IEC 61850 command originator category is remote.
3
Client IEC 61850 command originator category is station.
4
Station client reserves the control operating by writing controllable point LocSta.
5
Client IEC 61850 command originator category is remote.
6
Client IEC 61850 command originator category is station.
7
CTRL_STA unconnected in application configuration. Station client reserves the control operating
by writing controllable point LocSta.
1MRS759142 F
Basic functions
REX640
Technical Manual
141