5.8.7.1
CVPSOF Input signals
Table 1169: CVPSOF Input signals
Name
Type
Default
Description
I3P
SIGNAL
-
Three-phase currents
U3P
SIGNAL
-
Three-phase voltages
BLOCK
BOOLEAN
0=False
Block signal for acti-
vating the blocking
mode
CB_CL_CMD
BOOLEAN
0=False
External enabling of
SOTF by CB close
command
START
BOOLEAN
0=False
Start from function
to be accelerated by
SOTF
START_DLYD
BOOLEAN
0=False
Start from function
to be accelerated
with delay by SOTF
5.8.7.2
CVPSOF Output signals
Table 1170: CVPSOF Output signals
Name
Type
Description
OPERATE
BOOLEAN
Operate
5.8.8
CVPSOF Settings
Table 1171: CVPSOF Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Table 1172: CVPSOF Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation mode
1=Start
2=Current&voltage
3=Both
3=Both
Mode of operation
of SOTF Function
SOTF initialization
1=SwitchCommand
-2=Voltage or
SwitchCmd
-3=Current or
SwitchCmd
-4=Cur&Vol or
SwitchCmd
-2=Voltage or
SwitchCmd
Switch onto fault
initialization
Table continues on the next page
Protection related functions
1MRS759142 F
1228