excitation faults) to protect the system. The logic for the same has been shown in
.
The over/under fueling and over/under excitation logic will be checked
only if the local active and reactive power are above 2% of nominal value
respectively. When the local active and reactive power are less than 2%,
the
OPERATE
output is issued instantaneously.
Table 1347: Criteria for activation of STOP_ENGINE output
Fault type
Criteria
Output
Over fueling fault
MIN (P1 … P8) <
Min active power
That is, One among the network generators (ex-
cluding the local generator) enter reverse power
OR
F >
Max Freq limit
+
Max Freq deviation
STOP_ENGINE
Under fueling fault (MAX (P1 … P8) >
Max active power
That is, One among the network generators enter
over power region
OR
F <
Min Freq limit
–
Max Freq deviation
)
AND
P < 0.0
That is, local generator enters reverse power zone.
Table 1348: Criteria for activation of DE_EXCITE output
Fault type
Criteria
Output
Over excitation
fault
MIN(Q1 … Q8) <
Min reactive power
OR
Uavg >
Max voltage limit
+
Max Volts deviation
DE_EXCITE
Under excitation
fault
(Uavg <
Min voltage limit
–
Max Volts deviation
OR
I_MAX > 100% of nominal value
I_MAX = Maximum of the three phase currents ob-
tained from input I3P)
AND
Q < 0.0
That is, local generator enters reverse reactive pow-
er zone.
The activation of
STOP_ENGINE
or
DE_EXCITE
outputs, activates the
PRE_TRIP
output and initiates the operate delay timer. The timer characteristic is based on DT.
Once the time set by
Operate delay time elapses or when active power (for fueling