Name
Type
Default
Description
AVR_MODE_DRP
BOOLEAN
0=False
Automatic voltage
regulator mode
GEN_MOD_LOC
BOOLEAN
0=False
Generator in local
mode
BCKUP_PRT_ST
BOOLEAN
0=False
Backup protection ac-
tivated
ENG_LOD_UNLD
BOOLEAN
0=False
Engine loading or un-
loading in progress
RESET
BOOLEAN
0=False
Reset the correla-
tion and voting algo-
rithms and timer
7.5.7.2
DGMGAPC Output signals
Table 1350: DGMGAPC Output signals
Name
Type
Description
OPERATE
BOOLEAN
Operate
OPR_TIE_A
BOOLEAN
Operate tie breaker A
OPR_TIE_B
BOOLEAN
Operate tie breaker B
STOP_ENGINE
BOOLEAN
Stop fuel inflow to the engine
DE_EXCITE
BOOLEAN
De excite the generator
PRE_TRIP
BOOLEAN
Pre-trip signal indicating im-
minent trip of generator
FLT_DETECTED
BOOLEAN
Fault detected in the local
generator
OV_FUEL_FLT
BOOLEAN
Over fueling fault detected
UN_FUEL_FLT
BOOLEAN
Under fueling fault detected
OV_EXCT_FLT
BOOLEAN
Over excitation fault detected
UN_EXCT_FLT
BOOLEAN
Under excitation fault detec-
ted
GCB_TRP_FAIL
BOOLEAN
Trip command to generator
circuit breaker failed
TIE_TRP_FAIL
BOOLEAN
Trip command to tie breaker
failed
FUEL_RCK_FLT
BOOLEAN
Fault in fuel rack of the gover-
nor
I_EXCT_FLT
BOOLEAN
Fault in excitation system of
the generator
INT_BLKD
BOOLEAN
Internal block status
EXTERNAL_FLT
BOOLEAN
Gen P/Q not controlled due to
fault in external system
1MRS759142 F
Condition monitoring functions
REX640
Technical Manual
1423