96 Application macros
Hand control
This macro configures for drive control using only the control panel with no automated
control. Typically, this is a temporary configuration used prior to control wiring.
Parameters changed relative to HVAC default
Parameter
Value
Parameter
Value
9902
APPLIC MACRO
14 (HAND CONTROL)
3415
SIGNAL3 PARAM
100 (NOT SEL)
1001
EXT1 COMMANDS
0 (NOT SEL)
3416
SIGNAL3 MIN
(-)
1002
EXT2 COMMANDS
0 (NOT SEL)
3417
SIGNAL3 MAX
(-)
1106
REF3 SEL
2 (AI2)
3418
OUTPUT 3 DSP FORM (-)
1201
CONST SPEED SEL 0 (NOT SEL)
3419
OUTPUT 3 DSP UNIT
(-)
1301
MINIMUM AI1
0.0%
3420
OUTPUT 3 MIN
(-)
1304
MINIMUM AI2
0.0%
3421
OUTPUT 3 MAX
(-)
1401
RELAY OUTPUT 1
7 (STARTED)
4001
GAIN
1.0
1504
MINIMUM AO1
0.0mA
4002
INTEGRATION TIME
60.0 s
1510
MINIMUM AO2
0.0mA
4010
SETPOINT SEL
1 (AI1)
1601
RUN ENABLE
2 (DI2)
4101
GAIN
1.0
1608
START ENABLE 1
0 (NOT SEL)
4102
INTEGRATION TIME
60.0 s
2108
START INHIBIT
1 (ON)
4110
SETPOINT SEL
1 (AI1)
3207
SUPERV 3 PARAM
0103 (OUTPUT FREQ)
4210
SETPOINT SEL
1 (AI1)
1
SCR
2
AI1
3
AGND
4
10V
5
AI2
6
AGND
7
AO1
8
AGND
9
24V
10 GND
11 DCOM
12 DI1
13 DI2
14 DI3
15 DI4
16 DI5
17 RO1C
18 RO1A
19 RO1B
20 DOSRC
21 DOOUT
22 DOGND
External reference
0(2)…10 V or 0(4)…20 mA
Reference voltage 10 VDC
Output frequency:
0(4)…20 mA
Not Configured
Not Configured
Not Configured
Not Configured
Not Configured
Relay output 1 (P 1401)
Default operation:
Started
=>17 connected to 19
Digital output, max. 100 mA (P 1805)
No fault [Fault(-1)]
=>20 connected to 22
X1A
Analog input circuit common
PID feedback:
0(2)…10 V or 0(4)…20 mA
Analog output circuit common
Auxiliary voltage 24 VDC
Auxiliary voltage output common
Digital input common for all
Signal cable shield (screen)
Analog input circuit common
+
mA
+
X1B
Summary of Contents for ACS320 series
Page 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Page 4: ......
Page 18: ...18 Safety ...
Page 28: ...28 Operation principle and hardware description ...
Page 56: ...56 Electrical installation ...
Page 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Page 282: ...282 Actual signals and parameters ...
Page 358: ...358 Fieldbus control ...
Page 376: ...376 Fault tracing ...
Page 382: ...382 Maintenance and hardware diagnostics ...
Page 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Page 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Page 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Page 412: ...412 Dimension drawings ...
Page 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...