214 Actual signals and parameters
3404
OUTPUT1 DSP
FORM
0…9
1
5
Defines the decimal point location for the first
display parameter.
1…7 – Defines the decimal point location.
• Enter the number of digits desired to the
right of the decimal point.
• See table for example using pi
(3.14159).
8 = BAR METER – Specifies a bar meter
display.
9 = DIRECT – Decimal point location and
units of measure are identical to the
source signal. See
parameter listing for resolution
(which indicates the decimal point
location) and the units of measure.
3405
OUTPUT1 UNIT
0…127
1
4
Selects the units used with the first display parameter.
Note:
Parameter is not effective if parameter
= 9
(DIRECT).
3406
OUTPUT1 MIN
Depends on selection
1
-
Sets the minimum value displayed for the first display parameter.
Note:
Parameter is not effective if parameter
= 9
(DIRECT).
Group 34: Panel display
Code
Description
Range
Resolution
Default
S
3404 value Display
Range
0
+ 3
-32768…+32767
(Signed)
1
+ 3.1
2
+ 3.14
3
+ 3.142
4
3
0…65535
(Unsigned)
5
3.1
6
3.14
7
3.142
Note:
Parameters
are not effective.
0 = NOT SEL 12 = mV
24 = GPM
36 = l/s
48 = gal/m
60 = ft wg
1 = A
13 = kW
25 = PSI
37 = l/min
49 = gal/h
61 = lbsi
2 = V
14 = W
26 = CFM
38 = l/h
50 = ft
3
/s
62 = ms
3 = Hz
15 = kWh
27 = ft
39 = m
3
/s
51 = ft
3
/m
63 = Mrev
4 = %
16 = °F
28 = MGD
40 = m
3
/m
52 = ft
3
/h
64 = d
5 = s
17 = hp
29 = inHg
41 = kg/s
53 = lb/s
65 = inWC
6 = h
18 = MWh
30 = FPM
42 = kg/m
54 = lb/m
66 = m/min
7 = rpm
19 = m/s
31 = kb/s
43 = kg/h
55 = lb/h
67 = Nm
8 = kh
20 = m
3
/h
32 = kHz
44 = mbar
56 = FPS
68 = Km
3
/h
9 = °C
21 = dm
3
/s
33 = Ohm
45 = Pa
57 = ft/s
69 = min
10 = lb ft
22 = bar
34 = ppm
46 = GPS
58 = inH
2
O
70 = m
3
11 = mA
23 = kPa
35 = pps
47 = gal/s
59 = in wg
71 = m
6
72...116 = RESERVED (Values can be selected from the panel).
117 = %ref
119 = %dev
121 = % SP
123 = Iout
125 = Fout
127 = Vdc
118 = %act
120 = % LD
122 = %FBK
124 = Vout
126 = Tout
The following units are useful for the bar display:
117 = %ref, 118 = %ac, 119 = %dev, 120 = % LD, 121 =% SP, 122 = %FBK, 123 = Iout, 124 =
Vout, 125 = Fout, 126 = Tout, 127 = Vdc.
Summary of Contents for ACS320 series
Page 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Page 4: ......
Page 18: ...18 Safety ...
Page 28: ...28 Operation principle and hardware description ...
Page 56: ...56 Electrical installation ...
Page 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Page 282: ...282 Actual signals and parameters ...
Page 358: ...358 Fieldbus control ...
Page 376: ...376 Fault tracing ...
Page 382: ...382 Maintenance and hardware diagnostics ...
Page 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Page 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Page 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Page 412: ...412 Dimension drawings ...
Page 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...