Fieldbus control 315
Scaling drive feedback values
Feedback values are provided with units of percent, where 0% and 100% correspond
to the range of the sensor being used to measure the control variable. These points
have default units in Hz. If other units are required:
• Unbundle these points with appropriate slopes and intercepts.
• The new intercept equals the lowest value of the desired range.
• Calculate the new slope as follows:
Example
– You are controlling water temperature from a cooling tower using the
ACS320 to control a fan. The temperature sensor has a range of 30 to 250 degrees
Fahrenheit.
To unbundle the setpoint (INPUT REF 2), for commanding in degrees Fahrenheit,
where 0…60 Hz is equal to 30…250
°
F:
To unbundle the feedback (PRC PID FBCK) for monitoring in degrees Fahrenheit:
New Slope =
(Desired Range, ie, high - low values) x (Slope of Existing Point)
Range of Existing Point
=
(60 Hz - 0 Hz) x (0.01)
100% - 0%
= 0.006
New Slope =
(Desired Range) x (Slope of Existing Point)
Range of Existing Point
=
(250
°
F - 30
°
F) x (0.1)
100% - 0%
= 0.22
New Intercept = 30 (the temperature that corresponds to 0%)
New Slope =
(Desired Range) x (Slope of Existing Point)
Range of Existing Point
=
(250
°
F - 30
°
F) x (0.01)
100% - 0%
= 0.022
New Intercept = 30
Summary of Contents for ACS320 series
Page 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Page 4: ......
Page 18: ...18 Safety ...
Page 28: ...28 Operation principle and hardware description ...
Page 56: ...56 Electrical installation ...
Page 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Page 282: ...282 Actual signals and parameters ...
Page 358: ...358 Fieldbus control ...
Page 376: ...376 Fault tracing ...
Page 382: ...382 Maintenance and hardware diagnostics ...
Page 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Page 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Page 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Page 412: ...412 Dimension drawings ...
Page 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...