Actual signals and parameters 195
Group 22: Accel/Decel
This group defines ramps that control the rate of acceleration and deceleration. You
define these ramps as a pair, one for acceleration and one for deceleration. You can
define two pairs of ramps and use a digital input to select one or the other pair.
2115
MOT. HEATING SEL
-5...8
1
0
Selects the source for controlling motor heating.
-5...-1 = DI1 (INV)...DI5 (INV) – Inverted digital input DI. (0 = Motor heating is On, 1 =
Motor heating is Off).
0 (default) = OFF – Motor heating is inactive. Can also be used to switch off the
injection during heating.
1...5 = DI1...DI5 – Digital input DI1...DI5. (1 = Motor heating is On, 0 = Motor heating is
Off).
7 = COMM – Serial communication as the control for motor heating.
8 = ON – Motor heating active (during stop).
When motor heating is active, drive shows the alarm
Group 22: Accel/Decel
Code
Description
Range
Resolution
Default
S
2201
ACC/DEC 1/2 SEL
-5…7
1
0
Defines control for selection of acceleration/deceleration ramps.
• Ramps are defined in pairs, one each for acceleration and deceleration.
• See below for the ramp definition parameters.
0 = NOT SEL – Disables selection, the first ramp pair is used.
1 = DI1 – Defines digital input 1 as the control for ramp pair selection.
• Activating the digital input selects ramp pair 2.
• De-activating the digital input selects ramp pair 1.
2…5 = DI2…DI5 – Defines digital input DI2…DI5 as the control for ramp pair
selection.
• See DI1 above.
7 = COMM – Defines serial communication as the control for ramp pair selection.
-1 = DI1(INV) – Defines an inverted digital input 1 as the control for ramp pair
selection.
• De-activating the digital input selects ramp pair 2
• Activating the digital input selects ramp pair 1.
-2…-5 = DI2(INV)…DI5(INV) – Defines an inverted digital input DI2…DI5 as the
control for ramp pair selection.
• See DI1(INV) above.
2202
ACCELER TIME 1
0.0 … 1800.0 s
0.1 s
30.0 s
Sets the acceleration time for zero to maximum frequency for ramp pair 1. See A in
the figure with parameter
• Actual acceleration time also depends on parameter
Group 21: Start/Stop
Code
Description
Range
Resolution
Default
S
Summary of Contents for ACS320 series
Page 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Page 4: ......
Page 18: ...18 Safety ...
Page 28: ...28 Operation principle and hardware description ...
Page 56: ...56 Electrical installation ...
Page 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Page 282: ...282 Actual signals and parameters ...
Page 358: ...358 Fieldbus control ...
Page 376: ...376 Fault tracing ...
Page 382: ...382 Maintenance and hardware diagnostics ...
Page 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Page 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Page 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Page 412: ...412 Dimension drawings ...
Page 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...