Fieldbus control 301
Fault 31 – EFB1
For BACnet: If the drive’s control panel shows fault
, the drive has an
invalid Device Object Instance ID. To correct, use parameters 5311 and 5317 and
establish a unique drive ID that is in the range 1 to 4,194,303.
Faults 31…33 – EFB1…EFB3
Except as noted above, these three EFB fault codes (
…
) are
not used.
Intermittent off-line occurrences
The problems described above are the most common problems encountered with
ACS320 serial communication. Intermittent problems might also be caused by:
• Marginally loose connections,
• Wear on wires caused by equipment vibrations,
• Insufficient grounding and shielding on both the devices and on the
communication cables.
Summary of Contents for ACS320 series
Page 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Page 4: ......
Page 18: ...18 Safety ...
Page 28: ...28 Operation principle and hardware description ...
Page 56: ...56 Electrical installation ...
Page 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Page 282: ...282 Actual signals and parameters ...
Page 358: ...358 Fieldbus control ...
Page 376: ...376 Fault tracing ...
Page 382: ...382 Maintenance and hardware diagnostics ...
Page 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Page 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Page 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Page 412: ...412 Dimension drawings ...
Page 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...