132 Program features
User load curve
The user can specify a load curve (motor torque as a function of frequency) for
supervision. The curve is defined by five points. Supervision can be set for the torque
dropping below the underload curve, exceeding the overload curve, or both.
A fault is generated if the torque has been out of the allowed area for longer than the
user-defined time limit. An alarm is generated if the torque has been out of the
allowed area for longer than the half of the user-defined time limit.
Settings
Timed function status indicated through digital output DO
Timed PID1 parameter set 1/2 selection
Timed external PID2 activation
Parameter
Additional information
User load curve settings
Parameter
Additional information
Overload area
Underload area
Allowed operating area
Motor torque
(%)
Output
frequency
(Hz)
Freq. 2
Freq. 1
Freq. 3 Freq. 4
Freq. 5
Torque
high 1
Torque
high 2
Torque
high 3
Torque
low 1
Torque
low 2
Torque
low 3
Torque
high 4
Torque
low 4
Torque
high 5
Torque
low 5
Summary of Contents for ACS320 series
Page 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Page 4: ......
Page 18: ...18 Safety ...
Page 28: ...28 Operation principle and hardware description ...
Page 56: ...56 Electrical installation ...
Page 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Page 282: ...282 Actual signals and parameters ...
Page 358: ...358 Fieldbus control ...
Page 376: ...376 Fault tracing ...
Page 382: ...382 Maintenance and hardware diagnostics ...
Page 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Page 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Page 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Page 412: ...412 Dimension drawings ...
Page 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...