![ABB ACS320 series User Manual Download Page 332](http://html.mh-extra.com/html/abb/acs320-series/acs320-series_user-manual_2965332.webp)
332 Fieldbus control
BACnet protocol implementation conformance statement
(PICS)
BACnet Standard Device Profile
This version of ACS320 BACnet fully conforms to the 'Application-Specific Controller'
standard device profile (B-ASC).
Services Supported
The following services are supported by the ACS320:
• I-Am (Response to Who-Is, also broadcast on power-up & other reset)
• I-Have (Response to Who-Has)
• ReadProperty
• WriteProperty
• DeviceCommunicationControl
• ReinitializeDevice
Data Link Layer options
The ACS320 implements:
• MS/TP (Master), baud rate(s): 9600, 19200, 38400, 76800
• MS/TP (Slave), baud rate(s): 9600, 19200, 38400, 76800
MAC ID / Device Object Instance
The ACS320 supports separate MAC ID and Device Object Instance parameters:
• Set the MAC ID using drive parameter
. Default: 5302 = 1.
• Set the Device Object Instance ID using drive parameters 5311 and 5317.
Default: Both 5311 and 5317 = 0, which causes the MAC ID to “double” as the
Device Object Instance. For Device Object Instance values not linked to the MAC
ID, set ID values using 5311 and 5317:
- For IDs in the range 1 to 65,535: Parameter 5311sets the ID directly (5317
must be 0). For example, the following values set the ID to 49,134:
5311 = 49134 and 5317 = 0.
- For IDs > 65,335: The ID equals 5311’s value plus 10,000 times 5317’s value.
For example, the following values set the ID to 71,234:
5311 = 1234 and 5317 = 7.
Max Info Frames Property
Configure the Device Object Max Info Frames property using drive parameter 5312.
Default: 5312 = 1.
Summary of Contents for ACS320 series
Page 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Page 4: ......
Page 18: ...18 Safety ...
Page 28: ...28 Operation principle and hardware description ...
Page 56: ...56 Electrical installation ...
Page 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Page 282: ...282 Actual signals and parameters ...
Page 358: ...358 Fieldbus control ...
Page 376: ...376 Fault tracing ...
Page 382: ...382 Maintenance and hardware diagnostics ...
Page 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Page 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Page 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Page 412: ...412 Dimension drawings ...
Page 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...