![ABB ACS320 series User Manual Download Page 193](http://html.mh-extra.com/html/abb/acs320-series/acs320-series_user-manual_2965193.webp)
Actual signals and parameters 193
2103
DC MAGN TIME
0.00 … 10.00 s
0.01 s
0.30 s
Defines the pre-magnetizing time for the DC Magnetizing start mode.
• Use parameter
to select the start mode.
• After the start command, the drive pre-magnetizes the motor for the time defined
here, and then starts the motor.
• Set the pre-magnetizing time just long enough to allow full motor magnetization. Too
long a time heats the motor excessively.
2104
DC HOLD CTL
0...3
1
0
Enables or disables the Motor heating function. The function keeps the motor warm at
low temperatures.
0 = NOT SEL – Disables the Motor heating function.
1 = MOT. HEATING – Enables the Motor heating function. The function is activated by
parameter
.
2106
DC CURR REF
0 … 100%
1%
30%
Defines the DC current control reference as a percentage of parameter
.
2107
DC BRAKE TIME
0 … 250 s
0.1 s
0 s
Defines the DC brake time.
Note
: DC brake is activated when value is greater than 0.
2108
START INHIBIT
0, 1
1
0
Sets the Start inhibit function on or off. If the drive is not actively started and running,
the Start inhibit function ignores a pending start command in any of the following
situations and a new start command is required:
• Fault is reset.
• Run enable (parameter
) activates while start command is
active.
• Mode changes from local to remote.
• Control switches from EXT1 to EXT2Control switches from EXT2 toEXT1.
0 = OFF – Disables the Start inhibit function.
1 = ON – Enables the Start inhibit function.
Group 21: Start/Stop
Code
Description
Range
Resolution
Default
S
Summary of Contents for ACS320 series
Page 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Page 4: ......
Page 18: ...18 Safety ...
Page 28: ...28 Operation principle and hardware description ...
Page 56: ...56 Electrical installation ...
Page 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Page 282: ...282 Actual signals and parameters ...
Page 358: ...358 Fieldbus control ...
Page 376: ...376 Fault tracing ...
Page 382: ...382 Maintenance and hardware diagnostics ...
Page 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Page 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Page 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Page 412: ...412 Dimension drawings ...
Page 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...