238 Actual signals and parameters
4023
PID SLEEP LEVEL
0.0 … 120.0 Hz
0.1 Hz
0.0 Hz
Sets the motor speed / frequency that enables the PID sleep function – a motor speed
/ frequency below this level, for at least the time period
enables the PID sleep function (stopping the drive).
• Requires
= 7 INTERNAL.
• See figure: A = PID output level; B = PID process feedback.
4024
PID SLEEP DELAY
0.0 … 3600.0 s
0.1 s
60.0 s
Defines the delay for the sleep start function. See parameter
When the motor speed falls below the sleep level, the counter starts. When the motor
speed exceeds the sleep level, the counter is reset.
• See
above.
Group 40: Process PID set 1
Code
Description
Range
Resolution
Default
S
Wake-up level
deviation (
)
t
<
t
sd
Output
frequency
Selected process actual
value
Stop
t
sd
= Sleep delay
Sleep level
(4023)
Start
Wake-up delay
(
)
t
sd
Reference
t
Sleep boost step
Control
panel:
PID SLEEP
Sleep boost time (
t
t
Summary of Contents for ACS320 series
Page 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Page 4: ......
Page 18: ...18 Safety ...
Page 28: ...28 Operation principle and hardware description ...
Page 56: ...56 Electrical installation ...
Page 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Page 282: ...282 Actual signals and parameters ...
Page 358: ...358 Fieldbus control ...
Page 376: ...376 Fault tracing ...
Page 382: ...382 Maintenance and hardware diagnostics ...
Page 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Page 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Page 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Page 412: ...412 Dimension drawings ...
Page 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...