336 Fieldbus control
Modbus protocol technical data
Overview
The Modbus® protocol was introduced by Modicon, Inc. for use in control
environments featuring Modicon programmable controllers. Due to its ease of use
and implementation, this common PLC language was quickly adopted as a de-facto
standard for integration of a wide variety of master controllers and slave devices.
Modbus is a serial, asynchronous protocol. Transactions are half-duplex, featuring a
single Master controlling one or more Slaves. While RS232 can be used for point-to-
point communication between a single Master and a single Slave, a more common
implementation features a multi-drop EIA-485 network with a single Master
controlling multiple Slaves. The ACS320 features EIA-485 for its Modbus physical
interface.
RTU
The Modbus specification defines two distinct transmission modes: ASCII and RTU.
The ACS320 supports RTU only.
Feature summary
The following Modbus function codes are supported by the ACS320.
Function
Code
(Hex)
Description
Read Coil Status
0x01
Read discrete output status. For the ACS320, the individual
bits of the control word are mapped to Coils 1…16. Relay
outputs are mapped sequentially beginning with Coil 33 (eg,
RO1=Coil 33).
Read Discrete
Input Status
0x02
Read discrete inputs status. For the ACS320, the individual
bits of the status word are mapped to Inputs 1…16 or 1…32,
depending on the active profile. Terminal inputs are mapped
sequentially beginning with Input 33 (eg, DI1=Input 33).
Read Multiple
Holding Registers
0x03
Read multiple holding registers. For the ACS320, the entire
parameter set is mapped as holding registers, as well as
command, status and reference values.
Read Multiple
Input Registers
0x04
Read multiple input registers. For the ACS320, the 2 analog
input channels are mapped as input registers 1 & 2.
Force Single Coil
0x05
Write a single discrete output. For the ACS320, the individual
bits of the control word are mapped to Coils 1…16. Relay
outputs are mapped sequentially beginning with Coil 33 (eg,
RO1=Coil 33).
Write Single
Holding Register
0x06
Write single holding register. For the ACS320, the entire
parameter set is mapped as holding registers, as well as
command, status and reference values.
Diagnostics
0x08
Perform Modbus diagnostics. Subcodes for Query (0x00),
Restart (0x01) & Listen Only (0x04) are supported.
Force Multiple
Coils
0x0F
Write multiple discrete outputs. For the ACS320, the
individual bits of the control word are mapped to Coils 1…16.
Relay outputs are mapped sequentially beginning with Coil
33 (eg, RO1=Coil 33).
Summary of Contents for ACS320 series
Page 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Page 4: ......
Page 18: ...18 Safety ...
Page 28: ...28 Operation principle and hardware description ...
Page 56: ...56 Electrical installation ...
Page 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Page 282: ...282 Actual signals and parameters ...
Page 358: ...358 Fieldbus control ...
Page 376: ...376 Fault tracing ...
Page 382: ...382 Maintenance and hardware diagnostics ...
Page 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Page 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Page 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Page 412: ...412 Dimension drawings ...
Page 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...