![ABB ACS320 series User Manual Download Page 299](http://html.mh-extra.com/html/abb/acs320-series/acs320-series_user-manual_2965299.webp)
Fieldbus control 299
Diagnostics – EFB
Fault queue for drive diagnostics
For general ACS320 diagnostics information, see section
. The three most
recent ACS320 faults are reported to the fieldbus as defined below.
Serial communication diagnostics
Network problems can be caused by multiple sources. Some of these sources are:
• Loose connections
• Incorrect wiring (including swapped wires)
• Bad grounding
• Duplicate station numbers
• Incorrect setup of drives or other devices on the network
The major diagnostic features for fault tracing on an EFB network include
parameters
. Section
describes these
parameters in detail.
Diagnostic situations
The sub-sections below describe various diagnostic situations – the problem
symptoms and corrective actions.
Normal operation
During normal network operation,
…
parameter values act as follows at
each drive:
•
advances (advances for each application message
properly received and addressed to this drive).
•
does not advance at all (advances when an invalid
message CRC is received).
•
does not advance at all (advances when character
format errors are detected, such as parity or framing errors).
•
value varies depending on network traffic.
• BACnet protocol: 5316 EFB PAR 16 (MS/TP token counter) advances for each
token passed to this drive. (Does not apply for other protocols.)
Drive Parameter
Protocol Reference
Modbus
N2
FLN
BACnet
0401 Last Fault
40401
17
90
AV18
0412 Previous Fault 1
40402
18
91
AV19
0413 Previous Fault 2
40403
19
92
AV20
Summary of Contents for ACS320 series
Page 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Page 4: ......
Page 18: ...18 Safety ...
Page 28: ...28 Operation principle and hardware description ...
Page 56: ...56 Electrical installation ...
Page 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Page 282: ...282 Actual signals and parameters ...
Page 358: ...358 Fieldbus control ...
Page 376: ...376 Fault tracing ...
Page 382: ...382 Maintenance and hardware diagnostics ...
Page 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Page 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Page 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Page 412: ...412 Dimension drawings ...
Page 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...