Actual signals and parameters 207
3016
SUPPLY PHASE
Selects how the drive reacts to a supply phase loss, in other words, when the DC
voltage ripple is excessive.
0 = FAULT – Drive trips on fault
and the motor coasts to stop when
the DC voltage ripple exceeds 14% of the nominal DC voltage.
1 = LIMIT/ALARM – Drive output current is limited and alarm
generated when the DC voltage ripple exceeds 14% of the nominal DC voltage.
There is a 10 s delay between the activation of the alarm and the output current
limitation. The current is limited until the DC voltage ripple drops under the ripple
limit.
2 = ALARM – Drive generates alarm
exceeds 14% of the nominal DC voltage.
3017
EARTH FAULT
0…1
1
1
Defines the drive response if the drive detects a ground fault in the motor or motor
cables. The drive monitors for ground faults while the drive is running, and while the
drive is not running. Also see parameter
0 = DISABLE – No drive response to ground faults.
1 = ENABLE – Ground faults display fault
, and (if running) the
drive coasts to stop.
3018
COMM FAULT FUNC
0…3
1
0
Defines the drive response if the fieldbus communication is lost. The time delay is
defined by parameter
.
0 = NOT SEL – No response.
1 = FAULT – Displays fault
and the drive coasts to stop.
2 = CONST SP 7 – Displays warning
and sets speed using parameter
. This “alarm speed” remains active until the fieldbus
writes a new reference value.
3 = LAST SPEED – Displays warning
and sets speed using the last
operating level. This value is the average speed over the last 10 seconds. This
“alarm speed” remains active until the fieldbus writes a new reference value.
WARNING!
If you select CONST SP7, or LAST SPEED, make sure that
continued operation is safe when fieldbus communication is lost.
3019
COMM FAULT TIME
0.0 … 600.0 s
0.1 s
10.0 s
Sets the communication fault time used with parameter
• Brief interruptions in the fieldbus communication are not treated as faults if they are
less than the COMM FAULT TIME value.
3021
AI1 FAULT LIMIT
0.0 … 100.0%
0.1%
0.0%
Sets a fault level for analog input 1. See parameter
Do not set this limit below the level defined by parameter
.
• Value in percent of the full signal range.
3022
AI2 FAULT LIMIT
0.0 … 100.0%
0.1%
0.0%
Sets a fault level for analog input 2. See parameter
Do not set this limit below the level defined by parameter
.
• Value in percent of the full signal range.
Group 30: Fault functions
Code
Description
Range
Resolution
Default
S
Summary of Contents for ACS320 series
Page 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Page 4: ......
Page 18: ...18 Safety ...
Page 28: ...28 Operation principle and hardware description ...
Page 56: ...56 Electrical installation ...
Page 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Page 282: ...282 Actual signals and parameters ...
Page 358: ...358 Fieldbus control ...
Page 376: ...376 Fault tracing ...
Page 382: ...382 Maintenance and hardware diagnostics ...
Page 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Page 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Page 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Page 412: ...412 Dimension drawings ...
Page 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...