Actual signals and parameters 173
Group 13: Analogue inputs
This group defines the limits and the filtering for analog inputs.
Group 13: Analogue inputs
Code
Description
Range
Resolution
Default
S
1301
MINIMUM AI1
-100.0 … 100.0%
0.1%
20.0%
Defines the minimum value of the analog input.
• Define value as a percent of the full analog signal range. See example below.
• The minimum analog input signal corresponds to parameter
or
.
• MINIMUM AI cannot be greater than MAXIMUM AI.
• These parameters (reference and analog min. and max. settings) provide scale and
offset adjustment for the reference.
• See figure at parameter
.
Example:
To set the minimum analog input value to 4 mA:
• Configure the analog input for 0 … 20 mA current signal.
• Calculate the minimum (4 mA) as a percent of full range
(20 mA) = 4 mA / 20 mA * 100% = 20%
1302
MAXIMUM AI1
-100.0 … 100.0%
0.1%
20.0%
Defines the maximum value of the analog input.
• Define value as a percent of the full analog signal range.
• The maximum analog input signal corresponds to
• See figure at parameter
.
1303
FILTER AI1
0.0 … 10.0 s
0.1 s
0.1 s
Defines the filter time constant for analog
input 1 (AI1).
• The filtered signal reaches 63% of a step
change within the time specified.
1304
MINIMUM AI2
100.0 … 100.0%
0.1%
20.0%
Defines the minimum value of the analog input.
• See parameter
above.
1305
MAXIMUM AI2
-100.0 … 100.0%
0.1%
100.0%
Defines the maximum value of the analog input.
• See parameter
above.
1306
FILTER AI2
0.0 … 10.0 s
0.1 s
0.1 s
Defines the filter time constant for analog input 2 (AI2).
• See parameter
above
100
63
%
t
Unfiltered signal
Filtered signal
Time constant
Summary of Contents for ACS320 series
Page 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Page 4: ......
Page 18: ...18 Safety ...
Page 28: ...28 Operation principle and hardware description ...
Page 56: ...56 Electrical installation ...
Page 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Page 282: ...282 Actual signals and parameters ...
Page 358: ...358 Fieldbus control ...
Page 376: ...376 Fault tracing ...
Page 382: ...382 Maintenance and hardware diagnostics ...
Page 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Page 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Page 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Page 412: ...412 Dimension drawings ...
Page 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...