146 Actual signals and parameters
53 EFB PROTOCOL
Embedded fieldbus link settings. See chapter
on page
5301 EFB
PROTOCOL ID
Contains the identification and program version of the
protocol.
Note:
You can reset this parameter only with parameter
-
5302 EFB STATION
ID
Defines the address of the device. Two units with the
same address are not allowed on-line.
1
5303 EFB BAUD
RATE
Defines the transfer rate of the link
9.6 kbit/s
5304 EFB PARITY
Defines the use of parity and stop bit(s) and the data
length. The same setting must be used in all on-line
stations.
8 NONE 1
5305 EFB CTRL
PROFILE
Selects the communication profile. See section
.
5306 EFB OK
MESSAGES
Number of valid messages received by the drive.
During normal operation, this number increases
constantly.
0
5307 EFB CRC
ERRORS
Number of messages with an CRC (cyclic redundancy
check) error received by the drive. If the number is high,
check CRC calculation for possible errors.
Note:
High electromagnetic noise levels generate
errors.
0
5308 EFB UART
ERRORS
Number of messages with a character error received by
the drive.
0
5309 EFB STATUS
Status of the EFB protocol.
IDLE
5310 EFB PAR 10
Selects an actual value to be mapped to Modbus
register 40005.
0
5311 EFB PAR 11
Selects an actual value to be mapped to Modbus
register 40006.
0
5312 EFB PAR 12
Selects an actual value to be mapped to Modbus
register 40007.
0
5313 EFB PAR 13
Selects an actual value to be mapped to Modbus
register 40008.
0
5314 EFB PAR 14
Selects an actual value to be mapped to Modbus
register 40009.
0
5315 EFB PAR 15
Selects an actual value to be mapped to Modbus
register 40010.
0
5316 EFB PAR 16
Selects an actual value to be mapped to Modbus
register 40011.
0
5317 EFB PAR 17
Selects an actual value to be mapped to Modbus
register 40012.
0
5318 EFB PAR 18
For Modbus: Sets an additional delay before the drive
begins transmitting response to the master request.
0
5319 EFB PAR 19
ABB drives profile (ABB DRV LIM or ABB DRV FULL)
Control word. Read only copy of the Fieldbus Control
word.
0000 hex
Parameters in the short parameter view
No.
Name/Value
Description
Default
Summary of Contents for ACS320 series
Page 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Page 4: ......
Page 18: ...18 Safety ...
Page 28: ...28 Operation principle and hardware description ...
Page 56: ...56 Electrical installation ...
Page 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Page 282: ...282 Actual signals and parameters ...
Page 358: ...358 Fieldbus control ...
Page 376: ...376 Fault tracing ...
Page 382: ...382 Maintenance and hardware diagnostics ...
Page 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Page 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Page 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Page 412: ...412 Dimension drawings ...
Page 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...