94 Application macros
Dual setpoint with PID and constant speeds
This macro configures for applications with 2 constant speeds, active PID and PID
alternating between two setpoints using digital inputs. Set PID setpoints (internal to
the drive) using parameters 4011 (
SET
1) and 4111 (
SET
2). The digital input DI3 selects
the setpoints.
For more information see
Default values with different macros
on page
Parameters changed relative to HVAC default
Parameter
Value
Parameter
Value
9902
APPLIC MACRO
12 (DL SP PID CS)
4011
INTERNAL SETPNT
50.0%
1201
CONST SPEED SEL 10 (DI4, 5)
4027
PID 1 PARAM SET
3 (DI3)
1608
START ENABLE 1
0 (NOT SEL)
4110
SETPOINT SEL
19 (INTERNAL)
2108
START INHIBIT
1 (ON)
4111
INTERNAL SETPNT
100.0%
4010
SET POINT SEL
19 (INTERNAL)
1
SCR
2
AI1
3
AGND
4
10V
5
AI2
6
AGND
7
AO1
8
AGND
9
24V
10 GND
11 DCOM
12 DI1
13 DI2
14 DI3
15 DI4
16 DI5
17 RO1C
18 RO1A
19 RO1B
20 DOSRC
21 DOOUT
22 DOGND
External reference
0(2)…10 V or 0(4)…20 mA
Reference voltage 10 VDC
Output frequency:
0(4)…20 mA
Start/Stop:
Activate to start drive
D12 Presets/PID Selection:
Activate to select PID
D13 Setpoint Selection:
Activate to select Set 2
D14 Preset Speed 1
D15 Preset Speed 2
Relay output 1 (P 1401)
Default operation:
Started
=>17 connected to 19
Digital output, max. 100 mA (P 1805)
No fault [Fault(-1)]
=>20 connected to 22
X1A
Analog input circuit common
PID feedback:
0(2)…10 V or 0(4)…20 mA
Analog output circuit common
Auxiliary voltage 24 VDC
Auxiliary voltage output common
Digital input common for all
Signal cable shield (screen)
Analog input circuit common
+
mA
+
X1B
Summary of Contents for ACS320 series
Page 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Page 4: ......
Page 18: ...18 Safety ...
Page 28: ...28 Operation principle and hardware description ...
Page 56: ...56 Electrical installation ...
Page 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Page 282: ...282 Actual signals and parameters ...
Page 358: ...358 Fieldbus control ...
Page 376: ...376 Fault tracing ...
Page 382: ...382 Maintenance and hardware diagnostics ...
Page 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Page 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Page 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Page 412: ...412 Dimension drawings ...
Page 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...