Fieldbus control 347
DCU profile
The following tables describe the
CONTROL
WORD
content for the DCU profile.
6
RAMP_IN_
ZERO
1
RFG INPUT
ENABLED
Normal operation. Enter OPERATING.
0
RFG INPUT ZERO Force Ramp Function Generator input
to zero.
7
RESET
0=>1
RESET
Fault reset if an active fault exists (Enter
SWITCH-ON INHIBITED). Effective if
1604 = COMM.
0
OPERATING
Continue normal operation
8…9
Unused
10
Unused (ABB DRV LIM)
REMOTE_CMD
(ABB DRV
FULL)
1
Fieldbus control enabled.
0
• CW 0 or Ref 0: Retain last CW
and Ref.
• CW = 0 and Ref = 0: Fieldbus control
enabled.
• Ref and deceleration/acceleration
ramp are locked.
11
EXT CTRL LOC 1
EXT2 SELECT
Select external control location 2
(EXT2). Effective if 1102 = COMM.
0
EXT1 SELECT
Select external control location 1
(EXT1). Effective if 1102 = COMM.
12…15 Unused
DCU Profile
CONTROL
WORD
(See Parameter 0301)
Bit
Name
Value
Command/Req.
Comments
0
STOP
1
Stop
Stops according to either
the stop mode parameter or
the stop mode requests
(bits 7 and 8).
Simultaneous STOP and
START commands result in
a stop command.
0
(no op)
1
START
1
Start
0
(no op)
2
REVERSE
1
Reverse direction
This bit XOR’d with the sign
of the reference defines
direction.
0
Forward direction
3
LOCAL
1
Local mode
When the fieldbus sets this
bit, it steals control and the
drive moves to fieldbus local
control mode.
0
External mode
4
RESET
-> 1
Reset
Edge sensitive.
other
(no op)
5 EXT2
1
Switch
to
EXT2
0
Switch to EXT1
ABB Drives Profile (EFB)
CONTROL
WORD
Bit
Name
Value
Commanded
State
Comments
=/
=/
Summary of Contents for ACS320 series
Page 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Page 4: ......
Page 18: ...18 Safety ...
Page 28: ...28 Operation principle and hardware description ...
Page 56: ...56 Electrical installation ...
Page 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Page 282: ...282 Actual signals and parameters ...
Page 358: ...358 Fieldbus control ...
Page 376: ...376 Fault tracing ...
Page 382: ...382 Maintenance and hardware diagnostics ...
Page 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Page 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Page 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Page 412: ...412 Dimension drawings ...
Page 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...