Fieldbus control 323
65...
67
N/A
68
FLN LOC CTL
Commanded by FLN to temporarily “steal” start/stop
control of the drive from its normal source and place it
under FLN control. This functionality is analogous to
placing the drive in HAND mode at the panel, with the
control being taken by FLN instead. HAND mode at the
panel has priority over this point. Thus, this point is only
effective in temporarily taking control from the digital
inputs or some other internal control functionality.
69
FLN LOC REF
Commanded by FLN to temporarily “steal” input
reference control of the drive from its normal source and
place it under FLN control. This functionality is
analogous to placing the drive in HAND mode at the
panel, with the reference control being taken by FLN
instead. HAND mode at the panel has priority over this
point. Thus, this point is only effective in temporarily
taking control from the analog inputs or some other
internal control functionality.
70...
81
N/A
82
AI 1 ACTUAL
Indicates the input level of Analog Input 1.
0120
83
AI 2 ACTUAL
Indicates the input level of Analog Input 2.
0121
84
AO 1 ACTUAL
Indicates the output level of Analog Output 1.
0124
85
N/A
86
OK.ALARM
Indicates the current alarm state of the drive
(1 = ALARM, 0 = OK).
87
OK.MAINT
Indicates the current maintenance state of the drive
(1 = MAINT, 0 = OK).
Maintenance triggers are configured in drive parameter
Group 29.
88
ALARM WORD1 This point is a bit-field indicating active alarms in the
drive.
0308
89
ALARM WORD2 This point is a bit-field indicating active alarms in the
drive.
0309
90
LAST FAULT
This point is first in the drive's fault log and indicates the
most recent fault declared.
0401
91
PREV FAULT 1
This point is second in the drive's fault log and indicates
the previous fault declared.
0412
92
PREV FAULT 2
This point is last in the drive's fault log and indicates the
oldest fault in the log.
0413
93
OK.FAULT
Indicates the current fault state of the drive
(1 = FAULT, 0 = OK).
FLN Detailed Point Descriptions
Point
Description
Drive
Parameter
Summary of Contents for ACS320 series
Page 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Page 4: ......
Page 18: ...18 Safety ...
Page 28: ...28 Operation principle and hardware description ...
Page 56: ...56 Electrical installation ...
Page 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Page 282: ...282 Actual signals and parameters ...
Page 358: ...358 Fieldbus control ...
Page 376: ...376 Fault tracing ...
Page 382: ...382 Maintenance and hardware diagnostics ...
Page 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Page 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Page 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Page 412: ...412 Dimension drawings ...
Page 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...