296 Fieldbus control
Analog output control
Using the fieldbus for analog output control requires:
• Drive parameter values set as defined below.
• Fieldbus controller supplied reference word(s) in the appropriate location. (The
location is defined by the Protocol Reference, which is protocol dependent.)
PID control setpoint source
Use the following settings to select the fieldbus as the setpoint source for PID loops:
Communication fault
When using fieldbus control, specify the drive’s action if serial communication is lost.
Drive Parameter
Value
Setting
Protocol Reference
Modbus
N2
FLN BACnet
abb
drv
dcu
profile
1501 AO1
CONTENT SEL
135
(COMM VALUE
1)
Analog Output
1 controlled by
writing to
parameter
0135.
–
–
–
–
0135 COMM VALUE
1
–
40135
AO14 46
AO0
Drive Parameter
Value
Setting
Protocol Reference
Modbus
N2
FLN BACnet
abb
drv
dcu
profile
4010 SET
POINT
SEL (Set 1)
8 (COMM
VALUE 1)
9 (COMM +
AI1)
10
(COMM*AI1)
Setpoint is either:
Input Reference 2
(+/-/* AI1). Control
requires parameter
1106 value = comm.
Process PID setpoint.
Control requires
parameter 1106 value
= pid1 out and
parameter 4010 value
= comm.
40003
AO2 61
AV17
4110 SET
POINT
SEL (Set 2)
4210 SET
POINT
SEL
(Ext/Trim)
Drive Parameter
Value
Description
3018
COMM FAULT FUNC 0 (NOT SEL))
1 (FAULT)
2 (CONST SP7)
3 (LAST SPEED)
Set for appropriate drive response.
3019
COMM FAULT TIME Set time delay before acting on a communication loss.
Summary of Contents for ACS320 series
Page 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Page 4: ......
Page 18: ...18 Safety ...
Page 28: ...28 Operation principle and hardware description ...
Page 56: ...56 Electrical installation ...
Page 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Page 282: ...282 Actual signals and parameters ...
Page 358: ...358 Fieldbus control ...
Page 376: ...376 Fault tracing ...
Page 382: ...382 Maintenance and hardware diagnostics ...
Page 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Page 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Page 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Page 412: ...412 Dimension drawings ...
Page 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...