Fieldbus control 307
N2 binary output objects
The following table lists the N2 binary output objects defined for the ACS320 drive.
1.Requires optional MREL relay output card.
2.N2 LOCAL CTL and N2 LOCAL REF have priority over drive input terminals. Use these binary outputs for
temporary N2 control of the drive when
COMM
is not the selected control source.
AO14
COMMAND AO 1
135
10
%
0…100
AO16
EXT PID SETPOINT
4211
10
%
0…100
A019
MAILBOX PARAMETER
1
0…65535
A020
MAILBOX DATA
1
0…65535
N2 Binary Outputs:
Number
Object
Drive Parameter
Range
BO1
STOP/START
Command word
0 = Stop, 1 = Start to Speed
BO2
FORWARD/REVERSE
Command word
0 = Forward, 1 = Reverse
BO3
PANEL LOCK
Command word
0 = Open, 1 = Locked
BO4
RUN ENABLE
Command word
0 = Enable, 1 = Disable
BO5
REF1/REF2 SELECT
Command word
0 = Ref1, 1 = Ref2
BO6
FAULT RESET
Command word
Change 0 -> 1 Resets
BO7
COMMAND RO 1
134 (bit mask 01)
0 = Off, 1 = On
BO8
COMMAND RO 2
134 (bit mask 04)
0 = Off, 1 = On
1
BO9
COMMAND RO 3
134 (bit mask 08)
0 = Off, 1 = On
1
BO10
COMMAND RO 4
134 (bit mask 16)
0 = Off, 1 = On
1
BO13
RESET RUN TIME
114 (indirectly)
0 = N/A, 1 = On (Reset Run Time)
BO14
RESET KWH COUNT
115 (indirectly)
0 = N/A, 1 = On (Reset kWh Count)
BO15
PRC PID SELECT
4027 (indirectly)
0 = SET2, 1 = SET2
BO16
N2 LOCAL CTL
2
Command word
0 = Auto, 1 = N2
BO17
N2 LOCAL REF
2
Command word
0 = Auto, 1 = N2
BO18
SAVE PARAMETERS
1607 (indirectly)
0 = N/A, 1 = On (Save Parameters)
B019
READ MAILBOX
0 = No, 1 = Yes
B020
WRITE MAILBOX
0 = No, 1 = Yes
N2 Analog Outputs:
Number
Object
Drive
Parameter
Scale
Factor
Units
Range
Summary of Contents for ACS320 series
Page 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Page 4: ......
Page 18: ...18 Safety ...
Page 28: ...28 Operation principle and hardware description ...
Page 56: ...56 Electrical installation ...
Page 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Page 282: ...282 Actual signals and parameters ...
Page 358: ...358 Fieldbus control ...
Page 376: ...376 Fault tracing ...
Page 382: ...382 Maintenance and hardware diagnostics ...
Page 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Page 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Page 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Page 412: ...412 Dimension drawings ...
Page 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...