N2 binary input objects
The following table lists the N2 binary input objects defined for the ACS320 drive.
1.Require optional MREL relay output card.
N2 analog output objects
The following table lists the N2 analog output objects defined for the ACS320 drive.
N2 Binary Inputs:
Number
Object
Drive Parameter
Range
BI1
STOP/RUN
Status Word
0 = Stop, 1 = Drive Running
BI2
FORWARD/REVERSE
Status Word
0 = Forward, 1 = Reverse
BI3
FAULT STATUS
Status Word
0 = OK, 1 = Drive Fault
BI16
EXTERNAL 2 SELECT
Status Word
0 = EXT1 = EXT2
BI17
HAND/AUTO
Status Word
0 = AUTO, 1 = HAND
BI18
ALARM
Status Word
0 = OK, 1 = ALARM
BI19
MAINTENANCE REQ
Status Word
0 = OK, 1 = MAINT REQ
BI20
DRIVE READY
Status Word
0 = Not Ready, 1 = Ready
BI21
AT SETPOINT
Status Word
0 = No, 1 = At Setpoint
BI22
RUN ENABLED
Status Word
0 = Not Enabled, 1 = Enabled
BI23
N2 LOCAL MODE
Status Word
0 = Auto, 1 = N2 Local
BI24
N2 CONTROL SRC
Status Word
0 = No, 1 = Yes
BI25
N2 REF1 SRC
Status Word
0 = No, 1 = Yes
BI26
N2 REF2 SRC
Status Word
0 = No, 1 = Yes
N2 Analog Outputs:
Number
Object
Drive
Parameter
Scale
Factor
Units
Range
AO1
REFERENCE 1
Reference 1
10
%
0…100
AO2
REFERENCE 2
Reference 2
10
%
0…100
AO3
ACCEL TIME 1
2202
10
s
0.1…1800
AO4
DECEL TIME 1
2203
10
s
0.1…1800
AO5
CURRENT LIMIT
2003
10
A
0…1.3*I
2N
AO6
PID1-CONT GAIN
4001
10
%
0.1…100
AO7
PID1-CONT I-TIME
4002
10
s
0.1…600
AO8
PID1-CONT D-TIME
4003
10
s
0…10
AO9
PID1-CONT D FILTER
4004
10
s
0…10
AO10
PID2-CONT GAIN
4101
10
%
0.1…100
AO11
PID2-CONT I-TIME
4102
10
s
0.1…600
AO12
PID2-CONT D-TIME
4103
10
s
0…10
AO13
PID2-CONT D FILTER
4104
10
s
0…10
Summary of Contents for ACS320 series
Page 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Page 4: ......
Page 18: ...18 Safety ...
Page 28: ...28 Operation principle and hardware description ...
Page 56: ...56 Electrical installation ...
Page 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Page 282: ...282 Actual signals and parameters ...
Page 358: ...358 Fieldbus control ...
Page 376: ...376 Fault tracing ...
Page 382: ...382 Maintenance and hardware diagnostics ...
Page 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Page 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Page 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Page 412: ...412 Dimension drawings ...
Page 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...