![ABB ACS320 series User Manual Download Page 188](http://html.mh-extra.com/html/abb/acs320-series/acs320-series_user-manual_2965188.webp)
188 Actual signals and parameters
Group 18: Freq in & tran out
This group defines the frequency input and transistor output signal processing.
1707
OVERRIDE REF
Selects the source of the override reference.
1 = CONSTANT – Selects a preset frequency or speed for the override. The frequency
2 = PID – The reference is taken from the PID output, see group
.
Note:
The following conditions must be met when using PID in the override mode:
) can be either A1, A2 OR
INTERNAL PID1 parameter set 1 must be active (parameter
= set 1).
• Override direction (parameter
) can be either 0 = forward
or 7 = reverse.
Group 18: Freq in & tran out
Code
Description
Range
Resolution
Default
S
1801
FREQ INPUT MIN
0 … 16000 Hz
1 =1 Hz
0 Hz
Defines the minimum input value when DI5 is used as a frequency input. See section
on page
1802
FREQ INPUT MAX
0 … 16000 Hz
1 =1 Hz
1000 Hz
Defines the maximum input value when DI5 is used as a frequency input. See section
on page
1803
FILTER FREQ IN
0.0 … 10.0 s
1 = 0.1 s
0.1 s
Defines the filter time constant for frequency input, ie the time within 63% of a step
change is reached. See section
.
1804
TO MODE
DIGITAL
Selects the operation mode for the transistor output TO. See section
.
0 = DIGITAL – Transistor output is used as a digital output DO.
1 = FREQUENCY – Transistor output is used as a frequency output FO.
1805
DO SIGNAL
FAULT (-1)
Selects a drive status indicated through digital output DO. See parameter
1806
DO ON DELAY
0.0 … 3600.0 s
1 = 0.1 s
0.0 s
Defines the operation delay for digital output DO.
1807
DO OFF DELAY
0.0 … 3600.0 s
1 = 0.1 s
0.0 s
Defines the release delay for digital output DO.
1808
FO CONTENT SEL
0…178
104
Selects a drive signal to be connected to frequency output FO. Parameter index in
, for example, 102 = 0102 SPEED.
Group 17: Override
Code
Description
Range
Resolution
Default
S
Summary of Contents for ACS320 series
Page 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Page 4: ......
Page 18: ...18 Safety ...
Page 28: ...28 Operation principle and hardware description ...
Page 56: ...56 Electrical installation ...
Page 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Page 282: ...282 Actual signals and parameters ...
Page 358: ...358 Fieldbus control ...
Page 376: ...376 Fault tracing ...
Page 382: ...382 Maintenance and hardware diagnostics ...
Page 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Page 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Page 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Page 412: ...412 Dimension drawings ...
Page 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...