Actual signals and parameters 187
Group 17: Override
Code
Description
Range
Resolution
Default
S
1701
OVERRIDE SEL
-5…5
1
0
Selects the source of the override activation signal.
0 = NOT SEL – Override activation signal not selected.
1 = DI1 – Defines digital input DI1 as the override activation signal.
• This digital input must be activated for override activation signal.
2…5 = DI2…DI5 – Defines digital input DI2…DI5 as the override activation signal.
• See DI1 above.
-1 = DI1(INV) – Defines an inverted digital input DI1 as the override activation signal.
-2…-5 = DI2(INV)…DI5(INV) – Defines an inverted digital input DI2…DI5 as the
override activation signal.
• See DI1(INV) above.
1702
OVERRIDE FREQ
-500 … 500 Hz
0.1
0.0
Defines a preset frequency for the override.
1704
OVERR PASS CODE
0…65535
1
0
Entering the correct override pass code unlocks parameter
for one
change.
• Enter the pass code always before changing the value of the parameter
• The pass code is 358.
• The entry reverts back to zero automatically.
1705
OVERRIDE
0…2
1
0
Selects whether the override is enabled or disabled.
0 = OFF – Override disabled.
1 = ON – Override enabled.
• When enabled, the drive stores the values of all parameters into an override
parameter set (see parameter
) and the parameters in
will be write protected (except parameter
). To change the other parameters in
, override has to
be disabled.
2 = LOAD – Loads the saved override set into use (as an active parameter set).
1706
OVERRIDE DIR
Selects the source of the override direction signal.
0 = FORWARD – Assigns forward as the override direction.
1 = DI1 – Defines digital input 1 as the override direction signal.
• Activating the digital input selects the forward direction.
• De-activating the digital input selects the reverse direction.
2…5 = DI2…DI5 – Defines digital input DI2…DI5 as the override direction signal.
See DI1 above.
7 = REVERSE – Assigns reverse as the override direction.
-1 = DI1(INV) – Defines an inverted digital input DI1 as the override direction signal.
• De-activating the digital input selects the forward direction.
• Activating the digital input selects the reverse direction.
-2…-5 = DI2(INV)…DI5(INV) – Defines an inverted digital input DI2…DI5 as the
override direction signal.
• See DI1(INV) above.
Summary of Contents for ACS320 series
Page 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Page 4: ......
Page 18: ...18 Safety ...
Page 28: ...28 Operation principle and hardware description ...
Page 56: ...56 Electrical installation ...
Page 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Page 282: ...282 Actual signals and parameters ...
Page 358: ...358 Fieldbus control ...
Page 376: ...376 Fault tracing ...
Page 382: ...382 Maintenance and hardware diagnostics ...
Page 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Page 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Page 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Page 412: ...412 Dimension drawings ...
Page 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...