Fieldbus control 305
On the N2 fieldbus each ACS320 drive can be accessed by the full complement of
Metasys FMS features, including Change-of-State (COS) monitoring, alarm
notification, scheduling, trend, and totalization.
On one N2 fieldbus segment there can be up to 32 nodes while integrating ACS320
drives with Johnson Controls Metasys.
Drive device type
For the Metasys and Metasys Companion products, the device type for the ACS320
drive is VND.
N2 analog input objects
The following table lists the N2 analog Input objects defined for the ACS320 drive.
1.
RATED
SPEED
is a percent of maximum frequency (parameter 2008) if the drive is in scalar mode, and is a
percent of maximum speed (parameter 2002) in speed mode.
N2 Analog Inputs:
Number
Object
Drive
Parameter
Scale
Factor
Units
Range
AI1
OUTPUT FREQUENCY
0103
10
Hz
0…250
AI2
RATED SPEED
Note 1
10
%
0 …100
AI3
SPEED
0102
1
rpm
0 …9999
AI4
CURRENT
0104
10
A
0…9999
AI5
TORQUE
0105
10
%
-200…200
AI6
POWER
0106
10
kW
0…9999
AI7
DRIVE TEMPERATURE
0110
10
°
C
0 …125
AI8
KILOWATT HOURS
0115
1
kWh
0…65535
AI9
MEGAWATT HOURS
0141
1
MWh
0…65535
AI10
RUN TIME
0114
1
H
0…65535
AI11
DC BUS VOLTAGE
0107
1
V
0…999
AI12
OUTPUT VOLTAGE
0109
1
V
0…999
AI13
PRC PID FEEDBACK
0130
10
%
0…100
AI14
PRC PID DEVIATION
0132
10
%
0…100
AI15
EXT PID FEEDBACK
0131
10
%
0…100
AI16
EXT PID DEVIATION
0133
10
%
0…100
AI17
LAST FAULT
0401
1
fault code
AI18
PREV FAULT
0402
1
fault code
AI19
OLDEST FAULT
0403
1
fault code
AI20
AI 1 ACTUAL
0120
10
%
0…100
AI21
AI 2 ACTUAL
0121
10
%
0…100
AI22
AO 1 ACTUAL
0124
10
mA
0…20
AI24
MOTOR TEMP
0145
1
°
C
0…200
AI25
REVOLUTION CNT
0142
1
MREV
0…32767
Summary of Contents for ACS320 series
Page 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Page 4: ......
Page 18: ...18 Safety ...
Page 28: ...28 Operation principle and hardware description ...
Page 56: ...56 Electrical installation ...
Page 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Page 282: ...282 Actual signals and parameters ...
Page 358: ...358 Fieldbus control ...
Page 376: ...376 Fault tracing ...
Page 382: ...382 Maintenance and hardware diagnostics ...
Page 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Page 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Page 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Page 412: ...412 Dimension drawings ...
Page 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...