338 Fieldbus control
Modbus addressing
With Modbus, each function code implies access to a specific Modbus reference set.
Thus, the leading digit is not included in the address field of a Modbus message.
Note:
The drive supports the zero-based addressing of the Modbus specification.
Holding register 40002 is addressed as 0001 in a Modbus message. Similarly, coil 33
is addressed as 0032 in a Modbus message.
Refer again to section
above. The following sections describe, in
detail, the mapping to each Modbus reference set.
0xxxx Mapping – Modbus Coils.
The drive maps the following information to the
0xxxx Modbus set called Modbus Coils:
• Bit-wise map of the
CONTROL
WORD
(selected using parameter
). The first 32 coils are reserved for this purpose.
• Relay output states, numbered sequentially beginning with coil 00033.
The following table summarizes the 0xxxx reference set:
Modbus
Ref.
Internal Location
(All Profiles)
(5305 = 0)
(5305 = 1)
(5305 = 2)
0
0001
– Bit 0
OFF1*
STOP
OFF1*
0
0002
– Bit 1
OFF2*
START
OFF2*
0
0003
– Bit 2
OFF3*
REVERSE
OFF3*
0
0004
– Bit 3
START
LOCAL
START
0
0005
– Bit 4
N/A
RESET
RAMP_OUT_ZERO*
0
0006
– Bit 5
RAMP_HOLD*
EXT2
RAMP_HOLD*
0
0007
– Bit 6
RAMP_IN_ZERO* RUN_DISABLE
RAMP_IN_ZERO*
0
0008
– Bit 7
RESET
STPMODE_R
RESET
0
0009
– Bit 8
N/A
STPMODE_EM
N/A
0
0010
– Bit 9
N/A
STPMODE_C
N/A
0
0011
– Bit 10
N/A
RAMP_2
REMOTE_CMD*
0
0012
– Bit 11
EXT2
RAMP_OUT_0
EXT2
0
0013
– Bit 12
N/A
RAMP_HOLD
N/A
0
0014
– Bit 13
N/A
RAMP_IN_0
N/A
0
0015
– Bit 14
N/A
REQ_LOCALLOCK N/A
0
0016
– Bit 15
N/A
Reserved
N/A
0
0017
– Bit 16
Does not apply
FBLOCAL_CTL
Does not apply
0
0018
– Bit 17
FBLOCAL_REF
0
0019
– Bit 18
START_DISABLE1
0
0020
– Bit 19
START_DISABLE2
0
0021…
0
0032
Reserved
Reserved
Reserved
Reserved
Summary of Contents for ACS320 series
Page 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Page 4: ......
Page 18: ...18 Safety ...
Page 28: ...28 Operation principle and hardware description ...
Page 56: ...56 Electrical installation ...
Page 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Page 282: ...282 Actual signals and parameters ...
Page 358: ...358 Fieldbus control ...
Page 376: ...376 Fault tracing ...
Page 382: ...382 Maintenance and hardware diagnostics ...
Page 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Page 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Page 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Page 412: ...412 Dimension drawings ...
Page 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...