196 Actual signals and parameters
2203
DECELER TIME 1
0.0 … 1800.0 s
0.1 s
30.0 s
Sets the deceleration time for maximum frequency to zero for ramp pair 1.
• Actual deceleration time also depends on parameter
.
• See parameter
.
2204
RAMP SHAPE 1
0 … 1000.0 s
0.1 s
0.0
Selects the shape of the acceleration/deceleration
ramp for ramp pair 1. See B in the figure.
• Shape is defined as a ramp, unless additional
time is specified here to reach the maximum
frequency. A longer time provides a softer
transition at each end of the slope. The shape
becomes an s-curve.
• Rule of thumb: 1/5 is a suitable relation between
the ramp shape time and the acceleration ramp
time.
0.0 = LINEAR – Specifies linear
acceleration/deceleration ramps for ramp pair 1.
0.1…1000.0 – Specifies s-curve
acceleration/deceleration ramps for ramp pair 1.
2205
ACCELER TIME 2
0.0 … 1800.0 s
0.1 s
60.0 s
Sets the acceleration time (s) for zero to maximum frequency for ramp pair 2. See
parameter
2206
DECELER TIME 2
0.0 … 1800.0 s
0.1 s
60.0 s
Sets the deceleration time for maximum frequency to zero for ramp pair 2. See
parameter
2207
RAMP SHAPE 2
0 … 1000.0 s
0.1 s
0.0
Selects the shape of the acceleration/deceleration ramp for ramp pair 2. See
parameter
2208
EMERG DEC TIME
0.0 … 1800 s
0.1 s
1.0 s
Sets the deceleration time for maximum frequency to zero for an emergency.
• See parameter
• Ramp is linear.
Group 22: Accel/Decel
Code
Description
Range
Resolution
Default
S
T
FREQ
T
MAX
FREQ
Linear
S-curve
A
B
B (=0)
MAX
Summary of Contents for ACS320 series
Page 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Page 4: ......
Page 18: ...18 Safety ...
Page 28: ...28 Operation principle and hardware description ...
Page 56: ...56 Electrical installation ...
Page 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Page 282: ...282 Actual signals and parameters ...
Page 358: ...358 Fieldbus control ...
Page 376: ...376 Fault tracing ...
Page 382: ...382 Maintenance and hardware diagnostics ...
Page 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Page 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Page 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Page 412: ...412 Dimension drawings ...
Page 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...