194 Actual signals and parameters
2109
EMERG STOP SEL
-5…5
1
0
Defines control of the Emergency stop command. When activated:
• Emergency stop decelerates the motor using the emergency stop ramp (parameter
• Requires an external stop command and removal of the emergency stop command
before drive can restart.
0 = NOT SEL – Disables the Emergency stop function through digital inputs.
1 = DI1 – Defines digital input 1 as the control for Emergency stop command.
• Activating the digital input issues an Emergency stop command.
• De-activating the digital input removes the Emergency stop command.
2…5 = DI2…DI5 – Defines digital input DI2…DI5 as the control for Emergency stop
command.
• See DI1 above.
-1 = DI1(INV) – Defines an inverted digital input DI1 as the control for Emergency stop
command.
• De-activating the digital input issues an Emergency stop command.
• Activating the digital input removes the Emergency stop command.
-2…-5 = DI2(INV)…DI5(INV) – Defines an inverted digital input DI2…DI5 as the
control for Emergency stop command.
• See DI1(INV) above.
2110
TORQ BOOST CURR
15 … 300%
1
100%
Sets the maximum supplied current during torque boost.
• See parameter
.
2113
START DELAY
Defines the Start delay. After the conditions for start have been fulfilled, the drive waits
until the delay has elapsed and then starts the motor. Start delay can be used with all
start modes.
• If START DELAY = zero, the delay is disabled.
• During the Start delay, alarm 2028 START DELAY is shown.
2114
HEATING CURR REF
[%]
0.0...30.0%
0.1%
0.0%
Defines the amount of current to use for motor heating relative to the nominal current
of the motor.
Group 21: Start/Stop
Code
Description
Range
Resolution
Default
S
Summary of Contents for ACS320 series
Page 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Page 4: ......
Page 18: ...18 Safety ...
Page 28: ...28 Operation principle and hardware description ...
Page 56: ...56 Electrical installation ...
Page 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Page 282: ...282 Actual signals and parameters ...
Page 358: ...358 Fieldbus control ...
Page 376: ...376 Fault tracing ...
Page 382: ...382 Maintenance and hardware diagnostics ...
Page 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Page 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Page 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Page 412: ...412 Dimension drawings ...
Page 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...