![ABB ACS320 series User Manual Download Page 205](http://html.mh-extra.com/html/abb/acs320-series/acs320-series_user-manual_2965205.webp)
Actual signals and parameters 205
3006
MOT THERM TIME
256 … 9999 s
1
1050 s
Sets the motor thermal time
constant for the motor temperature
model.
• This is the time required for the
motor to reach 63% of the final
temperature with steady load.
• For thermal protection
according to UL requirements
for NEMA class motors, use the
rule of thumb: MOTOR THERM
TIME equals 35 times t6, where
t6 (in seconds) is specified by
the motor manufacturer as the time that the motor can safely operate at six times its
rated current.
• The thermal time for a Class 10 trip curve is 350 s, for a Class 20 trip curve 700 s,
and for a Class 30 trip curve 1050 s.
3007
MOT LOAD CURVE
50 … 150%
1
100%
Sets the maximum allowable operating
load of the motor.
• With the default value 100%, motor
overload protection is functioning
when the constant current exceeds
127% of the parameter
value.
• The default overloadability is at the
same level as what motor
manufacturer’s typically allow in the
30 °C (86 °F) ambient temperature
and 1000m (3300 ft) altitude. When
the ambient temperature exceeds 30
°C (86 °F) or the installation altitude
is over 1000m (3300 ft), decrease the parameter 3007 value according to the motor
manufacturer’s recommendation.
Example:
If the constant protection level needs to be 115% of the motor nominal
value to 91% (=115/127*100%).
3008
ZERO SPEED LOAD
25 … 150%
1
70%
Defines the load curve together with parameters
and
25%…150% = Allowed continuous motor load at zero speed in percent of the nominal
motor current.
Group 30: Fault functions
Code
Description
Range
Resolution
Default
S
Temp. rise
100%
63%
t
t
}
Motor load
Frequency
Output current (%) relative
to 9906 MOTOR NOM CURR
150
100
50
Summary of Contents for ACS320 series
Page 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Page 4: ......
Page 18: ...18 Safety ...
Page 28: ...28 Operation principle and hardware description ...
Page 56: ...56 Electrical installation ...
Page 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Page 282: ...282 Actual signals and parameters ...
Page 358: ...358 Fieldbus control ...
Page 376: ...376 Fault tracing ...
Page 382: ...382 Maintenance and hardware diagnostics ...
Page 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Page 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Page 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Page 412: ...412 Dimension drawings ...
Page 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...