Actual signals and parameters 201
2609
NOISE SMOOTHING
0, 1
1
0
Enables the noise smoothing function. Noise smoothing distributes the acoustic motor
noise over a range of frequencies instead of a single tonal frequency resulting in lower
peak noise intensity. A random component with an average of 0 Hz is added to the
switching frequency set by parameter
.
Note:
This parameter has no effect if parameter
= 16kHz.
0 = DISABLE
1 = ENABLE
2610
USER DEFINED U1
0 … 120% of
U
N
V
1 = 1 V
19% of
U
N
Defines the first voltage point of the custom U/f curve at the frequency defined by
parameter
.
2611
USER DEFINED F1
0.0 … 500.0 Hz
1 = 0.1 Hz
10.0 Hz
Defines the first frequency point of the custom U/f curve.
2612
USER DEFINED U2
0 … 120% of
U
N
V
1 = 1 V
38% of
U
N
Defines the second voltage point of the custom U/f curve at the frequency defined by
parameter
. See section
on page
.
2613
USER DEFINED F2
0.0 … 500.0 Hz
1 = 0.1 Hz
20.0 Hz
Defines the second frequency point of the custom U/f curve.
2614
USER DEFINED U3
0 … 120% of
U
N
V
1 = 1 V
47.5% of
U
N
Defines the third voltage point of the custom U/f curve at the frequency defined by
parameter
. See section
on page
.
2615
USER DEFINED F3
0.0 … 500.0 Hz
1 = 0.1 Hz
25.0 Hz
Defines the third frequency point of the custom U/f curve.
2616
USER DEFINED U4
0 … 120% of
U
N
V
1 = 1 V
76% of
U
N
Defines the fourth voltage point of the custom U/f curve at the frequency defined by
parameter
. See section
on page
.
2617
USER DEFINED F4
0.0 … 500.0 Hz
1 = 0.1 Hz
40.0 Hz
Defines the fourth frequency point of the custom U/f curve.
2618
FW VOLTAGE
0 … 120% of
U
N
V
1 = 1 V
95% of
U
N
Defines the voltage of the U/f curve when frequency is equal to or exceeds the motor
nominal frequency (
). See section
on page
.
2619
DC STABILISER
Enables or disables the DC voltage stabilizer. The DC stabilizer is used in scalar
control mode to prevent possible voltage oscillations in the drive DC bus caused by
motor load or weak supply network. In case of voltage variation the drive tunes the
frequency reference to stabilize the DC bus voltage and therefore the load torque
oscillation.
0 = DISABLE – Disables DC stabilizer.
1 = ENABLE – Enables DC stabilizer.
Group 26: Motor control
Code
Description
Range
Resolution
Default
S
Summary of Contents for ACS320 series
Page 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Page 4: ......
Page 18: ...18 Safety ...
Page 28: ...28 Operation principle and hardware description ...
Page 56: ...56 Electrical installation ...
Page 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Page 282: ...282 Actual signals and parameters ...
Page 358: ...358 Fieldbus control ...
Page 376: ...376 Fault tracing ...
Page 382: ...382 Maintenance and hardware diagnostics ...
Page 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Page 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Page 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Page 412: ...412 Dimension drawings ...
Page 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...