224 Actual signals and parameters
Group 37: User load curve
This new group defines supervision of user adjustable load curves (motor torque as a
function of frequency). The curve is defined by five points. - The function replaces
deleted underload parameters 3013…3015
3630
ALTERNATING
TIMER
0.0…1000.0 h
1
0.0 h
Defines the time interval for the timer to switch between On (1) and Off (0) states
(starting from the On state), based on the selections ALTERNATING or
ALT+BOOSTER in the timer source parameters
.
• ALTERNATING – Alternating time period is enabled. The time periods P1, P2,
P1+P2 and P3 are ignore for the specific timed function.
• ALT+BOOSTER – Alternating time period and booster times are enabled
simultaneously.
Group 37: User load curve
Code
Description
Range
Resolution
Default
S
3701
USER LOAD C
MODE
0...3
1
0
Supervision mode for the
user adjustable load
curves. This functionality
replaces the former
underload supervision in
.
0 = NOT SEL –
Supervision is not
active.
1 = UNDERLOAD –
Supervision for the
torque dropping
below the underload
curve.
2 = OVERLOAD –
Supervision for the
torque exceeding the
overload curve.
3 = BOTH – Supervision for the torque dropping below the underload curve or
exceeding the overload curve.
Group 36: Timed functions
Code
Description
Range
Resolution
Default
S
Overload area
Underload area
Allowed operating area
Motor torque (%)
Output frequency (Hz)
Summary of Contents for ACS320 series
Page 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Page 4: ......
Page 18: ...18 Safety ...
Page 28: ...28 Operation principle and hardware description ...
Page 56: ...56 Electrical installation ...
Page 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Page 282: ...282 Actual signals and parameters ...
Page 358: ...358 Fieldbus control ...
Page 376: ...376 Fault tracing ...
Page 382: ...382 Maintenance and hardware diagnostics ...
Page 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Page 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Page 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Page 412: ...412 Dimension drawings ...
Page 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...